Chapter 15.16 ELECTRICAL CODE ADOPTED
Section 15.16.030 Section 300-1(c) added--Conduit.
Section 300-1(c). All existing, new
and remodeled commercial, manufacturing and
industrial buildings, as well as multifamily buildings exceeding three stories in height shall be
wired for electricity in intermediate metal conduit, rigid metal conduit, rigid non-metallic
conduit, electrical metallic tubing, or metal-clad cable.
All Group R occupancies (single family
residential) as defined in Table No. 3-A of the 2001
California Building Code, Volume 1, not exceeding three stories in height shall be expressly
exempted from these requirements.
(Ord. 612 § 2, 2003)